UPS (Uninterrupted Power Supply)
Block
diagram and explanation of UPS
–
A computer requires a regulated, stabilized
power supply.
–
Fluctuations or sudden
power failures may cause damage to computers.
–
Thus, there is a need
of uninterrupted power supply i.e. UPS, to protect computer from these damages.
–
After, the A.C. mains
failure, UPS provides some backup time, to shut down computer system properly.
–
There are two types of
UPS, ON-line Ups and OFF-line UPS.
·
Schematic block diagram
of ON-lineUPS ( Uninterrupted Power
Supply) Online UPS
ON-
line UPS is also called as true UPS. The block diagram of ON-line UPS is shown
above.
It
has two power sources and transfer switch between them. Here, Battery is the
primary power source and utility power is the secondary power source.
Under
normal operation, the ON-line UPS is always running off the battery using
inverter, while the line power runs the battery charger. Therefore, it is
sometimes also called a double-conversion ON-line UPS. That means there is no transfer time in the
event of a power failure.
A
computer powered by an ON-line UPS responds to a power failure, keeps working
without interruption. The secondary power path provides backup in the event
that, the inverter fails or stutters due to some sort of internal problem.
The
most advantage of ON-line UPS is, the double-conversion process totally
isolates the output power from the input power.
These UPS are available in the range of
5000VA upto hundreds of thousands of VA.
The
disadvantage of ON-line UPS are: They are costlier than that of OFF-line UPS,
and it’s inefficiency. Because all the power going to the loads is converted
from A.C. to D.C. and back to A.C., which means much of the power is dissipated
as heat and it is occurring every time.
To
overcome this problem, a new design called a delta conversion ON-line UPS are
designed (delta means difference here). In this design, the battery charger is
replaced with a delta converter.
Instead
of providing all the output from the battery under normal circumstances, some
of it is provided directly by the delta converter from the input line power.
In
case of power failure, the delta converter stops operating and the unit acts
like a regular double-conversion ON-line UPS, since the inverter is also running
off the battery all the time.
Simplified
block schematic diagram of a delta conversion ON-line UPS is as shown below-
The converter and inverter both handle D.C. and A.C. current, providing the two power sources of the UPS. Bypassing the battery for part of the battery during normal operation reduces power consumption.
This new design
is available in large UPS (over 5000VA.)
- Off
Line UPS
OFF line UPS is actually a standby power
supply (SPS)
For the lower
end of budget scale mostly such UPS are used.
Here, the
primary power source is line power from the utility, and secondary power source
is the battery. It is called standby UPS because the battery and inverter are
normally not supplying power to the equipment.
The battery
charger is using line power to charge the battery and the battery with inverter
are waiting “on standby” until they are needed. When the mains A.C. power goes
out, the transfer switch changes to the secondary power source.
When line power
is restored, the UPS switches back.
The block
schematic diagram of OFF-line UPS is as shown in following fig.
The primary power source is filtered and surge-suppressed to protect against line noise and other problems that would not cause a switch to battery power.
The issue with
standby UPS is that, when the line power goes out the switch to battery power
happens very quickly, but not instantly. There is a delay of a fraction of a
second while the switch occurs, which is called the switch time or transfer
time of UPS. It is the time required for the UPS to switch from line to
battery power.
For a true
ON-line UPS this will be zero. But for Standby or OFF-line UPS it will be
normally few milliseconds. Hence, the Hold or hold-up time becomes important
here.
It
is the amount of time the power supply can handle having its input cut-off
before being interrupted.
If the transfer
time is equal or larger than the hold time, then the UPS is not useful.
The
hold up time is the amount of time the power supply will keep producing its
output, if it loses its input. Typical value is
20 mSec.
Standby UPS are
available in the range of 1000VA.
---------------------------------------------------------------------------------------------------------------------------
Comments
Post a Comment